99
Thermo King
Critical

High Compressor Pressure Ratio

Excessive pressure ratio detected between compressor suction and discharge, risking mechanical integrity.

Possible causes

  • Extremely low suction pressure due to lack of refrigerant
  • High discharge pressure due to dirty condenser
  • Obstructed expansion valve (TXV)
  • Evaporator or condenser fan failure

Recommended actions

  • Verify high and low pressures with gauges
  • Clean condenser coil and check airflow
  • Check refrigerant charge
  • Inspect solenoid valve operation