605
Thermo King
Warning

Check Fresh Air Temp Sensor

Fault in the sensor measuring outside ambient air temperature.

Possible causes

  • Physically damaged sensor
  • Connector exposed to moisture and corrosion
  • Broken wiring

Recommended actions

  • Check sensor location for obstructions
  • Measure circuit continuity
  • Replace sensor if reading is inconsistent