127
Thermo King
Info

Setpoint Not Entered (Zone)

An active zone in the multi-temperature system has been detected without a defined setpoint.

Possible causes

  • Operator failed to configure zone
  • Controller programming error
  • Loss of memory in zone configuration

Recommended actions

  • Enter a valid setpoint for the indicated zone
  • Verify zone ON/OFF configuration
  • Restart controller if reading error persists