123
Thermo King
Warning

Check Evap Coil Inlet Temp Sensor (CR)

Failure in the evaporator coil inlet temperature sensor (CR).

Possible causes

  • Defective inlet sensor
  • Sensor wires damaged by vibration
  • Moisture in the sensor connector
  • Problem with the controller input port

Recommended actions

  • Physically inspect sensor at the evaporator
  • Measure Ohms and compare with TK chart
  • Check harness for potential rubbing/chafing
  • Replace sensor if reading is erratic