110
Thermo King
Critical
Check Suction Line Sol Circuit (Zone)
Failure in the suction line solenoid valve circuit for a specific zone.
Possible causes
- Burnt zone suction coil
- Wiring failure between controller and zone
- Defective zone relay
- Corroded connection at remote evaporator
Recommended actions
- Verify power supply to suction solenoid
- Measure valve coil resistance
- Check for short circuit signs in zone harness
- Replace solenoid if no magnetism when energized