107
Thermo King
Critical

Check Condenser Inlet Sol Circuit

Error detected in the condenser inlet solenoid valve circuit.

Possible causes

  • Damaged condenser inlet coil
  • Open electrical circuit (cut wires)
  • Failed control relay
  • Poor ground connection

Recommended actions

  • Verify wire integrity near engine area
  • Measure solenoid coil resistance
  • Check output voltage from controller
  • Replace coil if out of specification