P00170
Carrier Transicold
Warning
Check LIV Circuit
Failure in the liquid injection valve (LIV) circuit.
Possible causes
- Defective LIV solenoid
- Clogged liquid filter
- Wiring issue from the controller
Recommended actions
- Check LIV coil resistance
- Confirm liquid flow to the compressor
- Replace coil if open or shorted