P00162
Carrier Transicold
Info

Check AFA Solenoid Circuit

Failure in the Automatic Fresh Air (AFA) regulator solenoid circuit.

Possible causes

  • Burned out AFA solenoid
  • Interrupted electrical connection
  • Mechanical obstruction in the damper

Recommended actions

  • Check AFA coil resistance
  • Lubricate the air damper mechanism
  • Check signal output from the controller