26106
Carrier Transicold
Critical

Sensor Supply Voltage 1 Low ENCU

The internal 5V sensor supply voltage in the ENCU is low.

Possible causes

  • Shorted sensor draining voltage
  • Damaged sensor harness
  • Defective ENCU internal regulator
  • Moisture in sensor connectors

Recommended actions

  • Disconnect sensors one by one to find short
  • Measure 5V output on reference wires
  • Check continuity to ground on signal lines
  • Replace ENCU if voltage remains low without sensors