24402
Carrier Transicold
Warning

Sensor Input Voltage High CCB4

Sensor input voltage on CCB4 board detected above the maximum limit.

Possible causes

  • Alternator / voltage regulator failure
  • Moisture in connectors
  • Sensor harness wires touching 12V lines
  • Board calibration error

Recommended actions

  • Measure alternator output voltage
  • Dry and clean sensor connectors
  • Check for short circuits between harness wires
  • Replace suspect sensor if voltage normalizes when disconnected