24201
Carrier Transicold
Warning
Sensor Input Voltage Low CCB2
Low sensor supply voltage on CCB2.
Possible causes
- Shorted sensor in compartment 2
- Voltage drop in long wiring
- CCB2 regulator failure
Recommended actions
- Check temperature and pressure sensors in C2
- Check cables for possible rubbing against chassis
- Measure voltage at CCB2 input terminals
- Replace CCB2 module if internal voltage is low