24101
Carrier Transicold
Warning

Sensor Input Voltage Low CCB1

Low sensor voltage on Compartment Control Board 1 (CCB1).

Possible causes

  • Overload on the 5V sensor line
  • Moisture in CCB1 connectors
  • Deficient main power supply

Recommended actions

  • Measure sensor supply voltage on CCB1
  • Inspect C1 sensors for short circuits
  • Dry and clean connectors if moisture is present
  • Verify power source stability