23100
Carrier Transicold
Critical

No Comm From Micro to Outbd1

Loss of communication between the microprocessor and Output Board 1 (Outbd1).

Possible causes

  • Loose or damaged communication harness
  • Power failure at Outbd1
  • Defective electronic output module

Recommended actions

  • Check wiring integrity between micro and Outbd1
  • Verify presence of 12V and ground at the board
  • Check status LEDs on Outbd1 board
  • Replace Output Board 1