00076
Carrier Transicold
Critical

Condenser Motor Overheated

The condenser fan motor thermal sensor reports excessive temperature.

Possible causes

  • Seized or burnt fan motor
  • Defective start/run capacitor
  • Obstructed fan blades
  • Extremely dirty condenser

Recommended actions

  • Rotate fan manually (with equipment off)
  • Test motor capacitor
  • Clean condenser coil with water/air
  • Verify motor current draw