E1
Bitzer
Critical

High Discharge Pressure (HP)

High pressure switch activated on Bitzer compressor.

Possible causes

  • Obstructed condenser
  • Condenser fans not operating
  • Refrigerant overcharge
  • Non-condensable air

Recommended actions

  • Clean condenser coil
  • Check fan startup
  • Recover and adjust charge

Can't find your code? Talk to an expert

$150

One-on-one phone session with a Low Temp refrigeration tech. Emergency temporary assistance only.

Have a question? Ask the community

Thousands of refrigeration mechanics read and answer for free. Post your case in under 1 minute.